Capacitive proximity sensors are similar to inductive proximity sensors. The main difference between the two types is that capacitive proximity sensors produce an electrostatic field
instead of an electromagnetic field. Capacitive proximity switches will sense metal as well as nonmetallic materials such as paper, glass, liquids, and cloth.
The sensing surface of a capacitive sensor is formed by two concentrically shaped metal electrodes of an unwound capacitor. When an object nears the sensing surface it enters the electrostatic field of the electrodes and changes the capacitance in an oscillator circuit. As a result, the oscillator
begins oscillating. The trigger circuit reads the oscillator’s amplitude and when it reaches a specific level the output state of the sensor changes. As the target moves away from the sensor the oscillator’s amplitude decreases, switching the sensor output back to its original state.
STANDARD TARGET AND DIELECTRIC CONSTANT
Standard targets are specified for each capacitive sensor. The standard target is usually defined as metal and/or water. Capacitive sensors depend on the dielectric constant of the target. The larger the dielectric number of a material the easier it is to detect. The following graph shows the relationship of the dielectric constant of a target and the sensor’s ability to detect the material based on the rated sensing distance (Sr).
The following table shows the dielectric constants of some materials. If, for example, a capacitive sensor has a rated sensing distance of 10 mm and the target is alcohol, the effective sensing distance (Sr) is approximately 85% of the rated distance, or 8.5 mm.
DETECTING THROUGH BARRIER
One application for capacitive proximity sensors is level detection through a barrier. For example, water has a much higher dielectric than plastic. This gives the sensor the ability to “see through” the plastic and detect the water.
SHIELDING
All capacitive sensors are shielded. These sensors will detect conductive material such as copper, aluminum, or conductive fluids, and nonconductive material such as glass, plastic, cloth, and paper. Shielded sensors can be flush mounted without adversely affecting their sensing characteristics. Care must be taken to ensure that this type of sensor is used in a dry environment. Liquid on the sensing